Radionics D6600 NetCom Guía de instalación Pagina 31

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 76
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 30
D9412G/D7412G Operation & Installation Guide
© 2002 Radionics Page 31 43488D
D9412G/D7412G
Power Outputs
5.4.5 Terminal 8
Terminal 8 provides continuous positive (+) 10.2 VDC to 13.9 VDC power. Relay C interrupts the power at Terminal
8 when activated. Use Terminal 8 to power smoke detectors or other devices that are reset by interrupting power.
One self-resetting circuit breaker protects Terminals 6, 7, and 8 against shorts.
Verification/Reset Relay
The default program sets Relay C (Terminal 8) as a verification/reset relay. See
Relay Parameters
and
Point
Assignments
in the
D9412G/D7412G Program Entry Guide
for instructions on programming verification/reset
relays and points.
Performing a Sensor Reset at a command center produces a five second relay activation of verification/reset
relays. The panel ignores verification/reset points during the five seconds of relay activation.
Vista de pagina 30
1 2 ... 26 27 28 29 30 31 32 33 34 35 36 ... 75 76

Comentarios a estos manuales

Sin comentarios